Common faults of pneumatic control valve and electric control valve

Time:

Dec 08,2022

Author:

Source:


Common faults cause Methods of prevention and elimination
Motor of electric regulating valve does not start     No input power turn on electricity
Broken wire or poor wire contact Change the wire or connect the wire correctly
Inconsistent power supply voltage or low voltage Check the voltage with an instrument
Thermal protection action (high ambient temperature or high frequency of use) Reduce the ambient temperature, reduce the use frequency or sensitivity
The power capacitor is broken down Replace input signal selection
Input signal error  
Self stop during automatic operation Overload protection due to excessive load Check the regulating valve to remove the overload
Thermal protection action Same as the previous item
Foreign matters caught in the regulating valve Even manual operation is very laborious. Remove the valve
Over tightening of packing gland Try loosening the gland
Manual operation is laborious Over tightening of packing gland Try loosening the gland
An accident occurred inside the valve Disassemble the valve for inspection
The opening signal is not fully closed The potentiometer is poorly installed. Check the installation of the potentiometer
The motor does not stop with the limit switch Poor adjustment of upper and lower limit given cam Readjust
Poor contact of stopper Replace the limit switch
Reduced control sensitivity and reduced motor torque Insufficient motor voltage Low or inconsistent power supply voltage
Low or inconsistent power supply voltage
oscillation Sensitivity is too high Adjust the sensitivity potentiometer to reduce the sensitivity